When showers are out of use, keep flushing the system!

When showers are out of use, keep flushing the system!

Since the start of the coronavirus crisis, every effort has been made to limit the spread of the virus. Public and commercial buildings were required to close for several prolonged periods. This caused considerable headaches for building managers and facility managers. One point of concern should not be overlooked: a prolonged closure affects the drinking water installation. Maintenance of these drinking water installations had to, and must, continue at all times. When they are no longer in use, or only partly in use, bacteria can easily establish themselves in the biofilm.

Legionella: a public health threat

The Legionella bacterium causes Legionnaires’ disease, a respiratory infection that affects people with chronic respiratory problems and people with a weakened immune system. The bacterium occurs naturally in water and develops where stagnant water and a source of nutrients are present, such as in biofilm in pipes or in rusty water storage tanks. The bacterium multiplies at temperatures of 20-45°C and can be harmful when inhaled in aerosol form. Schools, swimming pools, sports clubs and catering establishments are examples of public buildings where sanitary facilities are used intensively. During holidays or prolonged closures, however, drinking water is used little, if at all, which can accelerate biofilm formation in pipes. Larger commercial buildings often have facilities teams to draw up and implement a Legionella prevention plan, but in smaller buildings the responsibility lies with the owners. They, in turn, rely on local expertise to ensure that their installation complies with regulations. The solutions are simple: prevent the water from reaching temperatures at which bacteria multiply* and prevent water stagnation in the installation.

Keep flushing

It is mandatory to check the bacteriological quality of the water supply in every public building by taking regular samples and carrying out analyses. Additional tests for Legionella in the water must be carried out when levels of > 1,000 colony-forming units per litre (CFU/L) are measured, and remedial measures must be initiated from 10,000 CFU/L. The applicable regulations identify stagnant water in sanitary installations as a factor that promotes bacterial growth. The use of ring mains, or a closed loop, is therefore strongly recommended. European standard NF EN 806-5 also stipulates that parts of the installation that are rarely used must be flushed regularly. The recommended interval is once a week. The German guideline of April 2013, Hygiene in Trinkwasser-Installationen VDI/DVGW 6023, requires measures to refresh the water after the sanitary installation has been out of use for more than 72 hours.

Drinking water companies therefore advise building managers to continue implementing their Legionella prevention plans properly. Businesses without a Legionella prevention plan, whether mandatory or not, are also advised to flush pipes thoroughly before putting them back into use. This can be done by briefly opening all taps and letting the water run gently for one minute. Manual flushing, however, is labour-intensive and costly, particularly in larger installations.

Hot, hotter, hottest

The General requirements for water supply installations (NEN 1006) stipulate that hot water must be produced at a maximum temperature of 70°C, with the circulating water at 60°C. At this temperature, 90% of the bacteria die within 5 minutes*. If the temperature falls below this guideline, the risk of bacterial growth increases. Complex systems and long pipe runs lead to temperature drops and increase the risk of contamination. To limit this risk, the length of the branch pipes to draw-off points must be kept to a minimum. Pipe insulation prevents heat loss, while insulation where cold and hot water pipes run alongside each other prevents heat transfer. This stops the cold water temperature rising above 20°C, at which point Legionella bacteria are no longer inactive*.

Technical solutions in the fight against Legionella

DELABIE is strongly committed to tackling and preventing bacterial growth and offers a wide range of technical solutions. A central thermostatic mixing valve, for example, enables the building manager to maintain the prescribed temperatures in the system and ensure user safety. The thermostatic mixing valve must have anti-scalding protection that ensures the hot water is shut off automatically and immediately if the cold water supply fails, and vice versa. In addition, choosing electronic washbasin taps equipped with a periodic flushing function prevents water stagnation and, consequently, bacterial growth. Automatic flushing is activated every 24 hours after the last use and flushes for 60 seconds. An anti-stagnation solenoid valve, without a rubber diaphragm behind which a small amount of stagnant water is always left, is an additional advantage in the fight against bacterial growth. DELABIE is now introducing its new electronic thermostatic shower panel. This shower panel, also equipped with intelligent periodic flushing, draws water directly from the hot water supply at the specified temperature of 60°C and mixes it with cold water. The thermostatic mixing valve is integrated into the shower head, allowing mixed water at 38°C to be delivered immediately. There is no mixed water between the closed loop and the shower. Nor does water stagnate in the panel. Direct-flush toilet systems are also specifically designed for public sanitary facilities with high visitor numbers. Because the flush is connected directly to the water supply, there is no cistern containing stagnant water, and therefore no limescale or build-up of impurities, meaning there are no elements present that promote bacterial growth.

Managing contamination

If the water is found to be contaminated following a prolonged closure of the installation, point-of-use water filters can be used as a temporary control measure until a permanent and safe solution has been implemented. BIOFIL antibacterial filters for specific applications, with a service life of 2 months, provide peace of mind for both the building manager and the user. Thanks to innovative hollow-fibre membrane technology for microfiltering water, these filters have a large filtration surface for higher water volumes and high resistance to clogging, while remaining very compact. These point-of-use water filters are available for both washbasin and shower taps. Legionella prevention has long been a key public health priority. Reducing the risk of Legionella infection in public buildings presents specific challenges for user safety and system design. By understanding the risks and installing products specifically developed to meet these challenges, the risk of infection and scalding can be readily overcome. *

Source: Scientific and Technical Centre for the Construction Industry (WTCB: 2002)

A business enquiry for Delabie? Get in touch

Companies in this story

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ThemeFuture-proof water and sanitary systems
  • SubjectSanitaryware
  • CompanyDelabie
Share this article

Follow Installatie & Bouw Nederland

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.