Car park fire safety in accordance with CCV standards

Text Lieke BousemaImage Systemair

In overleg met het bevoegd gezag mocht Systemair de installatie in Lelystad één op één vervangen, waardoor de kosten voor de opdrachtgever relatief laag bleven.
In overleg met het bevoegd gezag mocht Systemair de installatie in Lelystad één op één vervangen, waardoor de kosten voor de opdrachtgever relatief laag bleven.

In spring 2025, Systemair refurbished and upgraded the ventilation system in an existing car park on Langstraat in Lelystad. The refurbishment was needed because one of the fans had started making a noise after almost twenty years of faithful service, says Niels de Harder, Industrial Account Manager, Car Park Ventilation at Systemair. “But, above all, it was to meet the current CCV standards.”

Legislation on fire safety in car parks changed in 2015, De Harder explains. “Since then, car park owners have also been responsible for the fire safety systems. In many cases, this affects the ventilation system, which is used not only to remove carbon monoxide and carbon dioxide, but also for smoke and heat extraction (SHE) in the event of a fire. This allows the fire brigade to get closer to the fire and tackle it more effectively.” 

The new system comprises three impulse fans to remove harmful exhaust gases and two extract fans that automatically ramp up in an emergency.

Independent inspection

Until 2015, suppliers of car park ventilation and smoke and heat extraction (SHE) systems were allowed to inspect and certify their own installations, but the legislation changed ten years ago. “Since then, installations have had to hold a CCV inspection certificate, which clearly sets out, among other things, the purpose of the installation and the applicable standards and legislation,” says De Harder. “An independent inspector (notified body) then assesses whether the fire protection system is still suitable for the current situation. Has the supplier done its job properly? Does the installation meet the requirements set out in the design basis document (UPD)? Like new installations, existing SHE systems must also meet CCV requirements.”

The car park in Lelystad covers approximately 1,250 m2. In accordance with the Bbl, the fans provide 3,375 m3/h of ventilation during normal operation, with a maximum of 13,500 m3/h.

Like-for-like replacement

“There are many existing car parks in the Netherlands with ventilation and SHE systems whose owners are unfortunately still unaware that a CCV inspection certificate is mandatory,” says De Harder. “The car park in Lelystad did not have one either. We took on the challenge on behalf of VvE and property manager Fidata. I contacted Lelystad Municipality directly and requested the old building file. Through a series of contacts, I then reached the local fire brigade and explained the situation. Based on the acquired rights, could we replace the car park ventilation system on a like-for-like basis, or did it need a full upgrade? And did we have to meet the new, more stringent legislation, or could we retain the standards in force when the car park was built, possibly with some additional requirements? After consulting the competent authority, we were allowed to replace the system on a like-for-like basis, keeping costs relatively low for the client. Naturally, without compromising on optimum indoor air quality or fire safety.” 

Along with the fans, Systemair also replaced the complete control system, control panels and gas detection systems.

Adequate visibility

“The new system comprises three impulse fans to remove harmful exhaust gases and two extract fans that automatically ramp up in an emergency,” says De Harder. “The car park in Lelystad covers approximately 1,250 m2. In accordance with the Besluit bouwwerken leefomgeving (Bbl), the fans provide 3,375 m3/h of ventilation during normal operation, with a maximum of 13,500 m3/h. In the event of a fire, however, the extract fans immediately ramp up to 31,250 m3/h, meaning the entire car park can be purged in six minutes. This removes enough smoke and heat to enable the fire brigade to keep the fire under control or tackle it.” 

Additional work

Along with the fans, Systemair also replaced the complete control system, control panels and gas detection systems, says Tjerk Baltjes, Project Manager, Car Park Ventilation. “We were able to retain all the fire-resistant cables. However, we applied new fire-resistant seals to the cable penetrations and separated the switch room with fire-resistant construction, preventing fire and smoke from spreading rapidly. The final work was completed at the end of April, and we handed our client the design basis document, a logbook containing the detailed design and product data, and a commissioning report. The car park now meets all current requirements.”    

A business enquiry for Systemair? Get in touch

Who worked on it

Parkeergarage Fidata Lelystad in Lelystad, renovation

  1. ventilation systemSystemair
  2. Owners' association and property managerFidata

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ProjectParkeergarage Fidata Lelystad
  • ThemeHealthy indoor air
  • SubjectFire safety
  • CompanySystemair
  • CompanyFidata
Share this article

Follow Installatie & Bouw Nederland

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.