Ned Air has designed 90 new air handling units specifically for the research greenhouses at Wageningen University & Research, where genetically modified crops are being tested. The units provide the ideal climate for the crops to grow optimally.

The nearly 15,000 square metres of new research greenhouses, where Wageningen University has been conducting tests with genetically modified crops since this autumn, are equipped with 90 new air handling units designed specifically for this application. A stable indoor climate is vital in the greenhouses, says Jeroen Stoel, key account manager at Ned Air. “The climate in a greenhouse determines the efficiency and quality of plant growth. Factors such as temperature, humidity and light are important elements in the growth of a crop.”

Ned Air therefore developed these bespoke air handling units in collaboration with Bosman van Zaal, which supplied the greenhouses. The units supply the greenhouses with fresh, conditioned air. The design was developed using BIM software. “Our R&D department worked closely with Bosman van Zaal’s design team to develop the design in BIM,” says Stoel. “After designing the units together in the BIM software, we built a prototype. We first tested it for its air-handling performance, followed by testing by Wageningen University.” When the air handling units were installed in the university’s new greenhouses, Stoel saw the benefits of the collaborative BIM design. “This meant that, during construction, we only had to take care of the finishing touches and details. We encountered far fewer surprises, so there were also fewer adjustments to make.”

The air handling units are no more than 1.40 metres high.

No leakage

Ned Air’s bespoke air handling units supply fresh, conditioned air to the specialist greenhouses, with no leakage permitted on either side. “We have to prevent contamination of the crops and stop pollen or other particles escaping,” explains Stoel. “That is why we have installed a two-stage filtration system, so the filters remove more particles from the air and also last longer.” The first filter section contains an ISO1680 ePM1 80% filter, while the second has an Absolute HEPA H14 filter. Both filters are installed so they can be replaced from inside the greenhouse.

The design in BIM.

Corridors

Ned Air also ensured that the air handling units are no more than 1.40 metres high, to prevent their shadows falling on the crops. For the same reason, the pipe mounted on top of each unit, which supplies the greenhouses with the required air, is made of transparent Plexiglas. The units are located in the so-called service corridors between the greenhouses. Large central air handling units supplied by the company are also installed in these corridors. They are equipped with heat recovery and supply the greenhouses with fresh outdoor air, which is needed to create the required positive pressure inside them.

Ned Air delivered all the units from the beginning of 2020 over a period of a few months. As everything still needed to be properly adjusted, commissioning took place shortly after the summer.    

A business enquiry for Ned Air? Get in touch

Companies in this story

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ThemeHealthy indoor air
  • SubjectGeneral
  • CompanyNed Air
Share this article

Follow Installatie & Bouw Nederland

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.