General

Car park ventilation is specialist work

Aan de plafonds boven de rijbanen heeftSystemair drie stuwdrukventilatoren opgehangen, die de ruimtelucht geforceerd opmengen en transporteren richting de afvoerventilatoren.
Aan de plafonds boven de rijbanen heeftSystemair drie stuwdrukventilatoren opgehangen, die de ruimtelucht geforceerd opmengen en transporteren richting de afvoerventilatoren.

Jet fan ventilation system provides optimum extraction of exhaust gases, smoke and heat

Rosmalen has gained a stunning new green residential neighbourhood: De Hoef. On the former football pitches of O.J.C. Rosmalen, 62 nearly zero-energy apartments and 26 homes with gardens have been built in phases. A single-storey car park with 92 parking spaces and an area of 2,560 m2 has also been provided beneath the apartments, approximately 2 metres below ground level. The construction work was carried out by Van Santvoort Bouw, while Sankomij Installatietechniek was responsible for the building services. Its work ranges from plumbing to heating and ventilation, and from consultancy to installation and maintenance. For the car park’s smoke and heat exhaust system (RWA) and fire ventilation, the Veldhoven-based installer contacted Systemair.

A single-storey car park with 92 parking spaces and an area of 2,560 m2 has been provided beneath the apartments, approximately 2 metres below ground level.

Choosing Systemair was a logical decision, says Leon van Zomeren, Project Manager at Sankomij Installatietechniek. “We have already completed several successful projects together. What we particularly value about Systemair is its solution-oriented approach. From the outset, it not only helps us consider the systems, but also makes suggestions for optimisation. The car park at De Hoef is an excellent example of this.”

Equivalence

“Whenever we receive an enquiry about car park ventilation, we always ask an important follow-up question,” says Niels de Harder, Industrial Account Manager at Systemair. “Is the mechanical ventilation intended solely to keep concentrations of hazardous gases such as carbon monoxide (CO) as low as possible? Or must the system also be suitable for use in firefighting? Under the 2012 Building Decree, equivalence must be demonstrated for spaces larger than 1,000 m2.”

Minimal exceedance

No solution had yet been developed for firefighting in the car park at De Hoef, says De Harder. “One idea put forward by the consultant was to use fire ventilation. However, the car park in Rosmalen has an area of 2,560 m2, which made fire ventilation more complex. Under the fire ventilation standard (NEN 6098), spaces of up to 2,500 m2 can be served by F300-certified axial fans, which can extract 140,000 m3/h of air. For spaces larger than 2,500 m2, however, fire ventilation must be designed using a Computational Fluid Dynamics (CFD) simulation, and larger, heavier and more expensive fans are required. As the car park compartment exceeded the limit only marginally, we advised adding a number of storage rooms, an extra space or partition walls, so that the area to be ventilated would remain within the 2,500 m2 limit.”

Three AXC 900 medium-pressure axial fans have been installed where the air is discharged outside.

A practical, cost-effective and safe solution 

“Together with Systemair, the building services consultant and the competent authority (the fire brigade), we arrived at a practical, cost-effective and safe solution for the car park,” says Van Zomeren. “At the request of Systemair and Sankomij, the client commissioned a CFD simulation, which demonstrated and substantiated that smoke could be extracted from the car park within the required time in the event of a fire. On this basis, we received approval to treat the 2,560 m2 car park as a 2,500 m2 car park. This was also confirmed in the fire protection design document, allowing us to use a fixed flow rate of 140,000 m3/h without smoke curtains.” 

Precisely designed ventilation and smoke and heat exhaust

In normal daily use, the car park is naturally ventilated through grilles at the entrances and exits. If CO concentrations rise, however, Systemair’s jet fans are activated. “We have suspended three jet fans from the ceilings above the traffic lanes. They mechanically mix the air in the space and propel it towards the extract fans,” says De Harder. “We have also installed three AXC 900 medium-pressure axial fans at the air discharge point. Two of these fans run at 20% of their capacity during normal operation. In an emergency, they automatically switch to 100%. The third fan is also brought into operation.”

Systemair’s fans are controlled by a bespoke control panel installed in a fire-compartmented plant room.

Three-minute delay

Systemair’s fans are controlled by a bespoke control panel installed in a fire-compartmented plant room. “The control panel has both visual (a light) and audible alarms and is continuously connected to the fire alarm system,” says De Harder. “When an emergency is detected, the control panel waits for three minutes. If the fans were to start immediately, the mixing of smoke and air in the space would obstruct visibility for residents and visitors in the car park. During the first three minutes, the smoke spreads like a blanket along the ceiling. Residents and visitors can leave the car park safely during this period, after which the fans forcibly extract all the smoke and heat. This also allows the fire brigade to work safely.”     

A business enquiry for Systemair? Get in touch

Who worked on it

De Hoef in 's-Hertogenbosch

  1. stuwdrukventilatorenSystemair
  2. mechanical installationsSankomij Installatietechniek

Keep following this

Get an email when a new story is published. No account needed.