Certified variable-speed smoke and heat exhaust fans for safer, greener buildings

The 2015 revision of the European standard for mechanical smoke and heat exhaust (SHE) fans opened up opportunities to use smoke extract fans with variable frequency drives in the event of a fire. By comprehensively certifying the SHE fans together with the variable frequency drive, new opportunities were created for safer, greener and more energy-efficient solutions. Even so, many people have yet to discover certified variable-speed SHE fans.
Increasing the safety of a high-rise building, car park or tunnel while also reducing operating costs may sound like a utopian ideal. But changes made to the NEN-EN 12101-3 standard for mechanical SHE fans in 2015 have brought this scenario within reach. The standard sets out three options for controlling SHE fans:
- Run the smoke extract fan at the rated motor speed without a variable frequency drive. This requires only a certified SHE fan. A variable frequency drive can be used for other operating points, but it must be bypassed in the event of a fire. This means that smoke extraction can only run at a single speed, which considerably limits flexibility. In addition, the bypass option requires extra (costly) control equipment in the control cabinet.
- Use an SHE fan in combination with a variable frequency drive, without certifying them together for fire conditions. With this set-up, the available motor power must be reduced by 20%. An additional LC low-pass filter, such as a sine-wave filter, must also be installed between the variable frequency drive and the motor, significantly increasing costs. Costs will rise further because the variable frequency drive, emergency power supply and cabling must also be designed to provide the extra 20% energy reserve.
- Use a certified package comprising an SHE fan and variable frequency drive, with the complete package tested and certified for smoke and heat exhaust systems in accordance with the standard. This solution allows the full potential of the package to be realised.
The final option, a certified package comprising a smoke exhaust fan and variable frequency drive, enables building managers to use variable-speed fans in the event of a fire. The result? Maximum reliability combined with lower operating costs and the flexibility to control smoke management and extraction.
In a property market that is increasingly inclined to build upwards, the requirements for reliable smoke ventilation systems are also becoming more demanding. The need for ventilation systems that create safe escape routes, assist the fire service with smoke extraction and protect the building is a critical factor.
From energy waste to energy savings
Variable frequency drives can control the fan at any required capacity. In effect, the fans serve a dual purpose, as their full operating range can be used both for normal ventilation and in the event of a fire. Within the EU, options 1 and 2 above apply to SHE fans that are not certified together with a variable frequency drive. But if you choose a certified combination of an SHE fan and variable frequency drive, you can be sure it complies with the applicable regulations.
Jos Wissink, Business Development Manager at NOVENCO Building & Industry, says: “Now that high-efficiency fans with variable speed control are also available as a certified package for smoke and heat exhaust, building managers can achieve a more cost-effective set-up: maximum energy savings and a state-of-the-art SHE system in a single solution.”.
Going green: additional cost-saving benefits
As high-efficiency SHE fans reduce power consumption, the required power supply and the associated costs of control systems can also be reduced. In addition to energy savings, further upfront savings can be achieved through smaller power cables and lower costs for normal and emergency power supplies.
Although the installation costs of a certified package comprising an SHE fan and variable frequency drive are higher than those of other alternatives, the total upfront investment and operating costs are reduced to such an extent that the investment is highly attractive. The key is to consider the total lifecycle costs, rather than just one element of the package.
A comparison of similar NOVENCO product ranges shows the differences between industry-standard solutions such as the NovAx™ range and the high-efficiency ZerAx® SHE fan range. With all selection variables set to the same values, the electrical input power of a NovAx™ SHE fan is 65kW, compared with 56kW for a ZerAx® of the same size. The difference in power consumption is almost 14%, resulting in significantly lower operating costs. In addition, the power supply, including the UPS systems, can be sized 14% smaller, reducing upfront investment costs. And with a considerably lower noise level, the high-quality ZerAx® is the obvious choice.
High efficiency and low noise levels
One of the most appealing features of choosing a certified package comprising an SHE fan and variable frequency drive is its efficiency. This affects operating costs, reduces CO2 emissions and benefits the environment. NOVENCO’s ZerAx® axial fans achieve efficiencies of up to 92% and an impressive recycling rate of 98% after more than 20 years in operation, as documented in a recycling analysis by Stena Recycling. This makes it the most efficient and probably also the most sustainable SHE fan on the market today.
At the same time, the fan’s optimised aerodynamic design results in extremely low noise levels. In normal ventilation mode, less sound attenuation is needed, and silencers can be smaller or even omitted altogether. This results in lower system resistance, which in turn reduces the power required. In short, both installation and operating costs are positively affected.
When safety comes first
Some would say that the cost reductions are an added bonus. The main benefit is that you can rely on the highly reliable ZerAx® SHE fans in combination with Danfoss VLT® variable frequency drives. They are designed to do the job when it matters: they operate as a certified emergency system that will not fail.
If your emergency system fails, lives are at risk. Knowing that the SHE fan has been tested and certified for use at high smoke temperatures provides peace of mind. The certified ZerAx® and Danfoss VLT® package creates safe escape routes for occupants, assists the fire service in fighting fires and protects property. Reliability is central, and choosing a certified solution guarantees that the fans can withstand prolonged smoke and heat extraction.
When safety is also your top priority, a certified package comprising an SHE fan with variable speed control is the obvious choice, simply because it is reliable in every respect.