General

From gas-fired heating to all-electric, while retaining the existing heat emitters

From gas-fired heating to all-electric, while retaining the existing heat emitters

A prominent multi-tenant office building in Tilburg has undergone a major sustainability upgrade early this year. “Until recently, the 5,000-square-metre building was heated by gas-fired boilers,” says Cees van de Groep, commercial technical adviser at Airview Luchtbehandeling BV. “As the boilers had reached the end of their technical life and the property owner wanted to move away from gas, a sustainable all-electric alternative was sought. On behalf of installer J. Ketelaars-Vromans, we supplied two Clivet WSAN-XEM HW 60.4 air-to-water heat pumps. These high-temperature heat pumps have a total heating capacity of 260 kW at an outdoor temperature of -10°C and are an excellent fit for the project’s sustainability ambitions.”

“By adding extra insulation to the building, we were able to retain the existing central heating emitters (radiators), and the building no longer needs a high-temperature heating circuit (90-70°C). Instead, the water circuit is now set to 60-50°C,” says Van de Groep. “This also made the changeover considerably easier.”

The high-temperature heat pumps have a total heating capacity of 260 kW at an outdoor temperature of -10°C and are an excellent fit for the project’s sustainability ambitions.

High-temperature heat pumps

“To ensure sufficient heat output, the installer was looking for a high-temperature heat pump. The system also had to meet demanding efficiency requirements,” he says. “Airview is increasingly offering this solution, which has now also been installed in the multi-tenant office building in Tilburg. It is the first project Airview has completed for J. Ketelaars-Vromans. The Clivet WSAN-XEM HW 60.4 air-to-water heat pumps meet the specified requirements very well and are an ideal solution for heating in winter and cooling in summer. As standard, the units can operate at outdoor air temperatures as low as -15° in heating mode and -10°C in cooling mode. The maximum leaving water temperature is 65°C.”

Maximum comfort, minimum energy costs

The Clivet WSAN-XEM HW air-to-water heat pumps are fitted with automatic, variable-speed inverter circulation pumps, which make the system considerably simpler. “This means there is no longer any need for external 3-way mixing valves to keep the return water at the required temperature,” says Van de Groep. “Once the target temperature has been reached, the system maintains it by operating at a low level, keeping energy consumption to a minimum. If the temperature starts to deviate from the setpoint, the system automatically increases its capacity. This so-called Vari Flow principle makes both cooling and heating considerably more efficient. Users do not notice the temperature fluctuations, but enjoy consistently high levels of comfort at minimum energy cost.”

The air-to-water heat pumps in Tilburg are installed in a master/slave configuration. “An advanced control system ensures that the heat pumps run for the same number of hours and that the system is used as efficiently as possible, depending on the demand for heating and/or cooling. Optimising part-load operation minimises energy consumption over the system’s entire service life.”

By adding extra insulation to the building, the existing central heating emitters (radiators) could be retained, and the building no longer needs a high-temperature heating circuit (90-70°C). Instead, the water circuit is now set to 60-50°C.

Reliable operation, optimum service life

The Clivet WSAN-XEM HW air-to-water heat pumps are fitted as standard with electronic expansion valves and special compressors with a hot-gas bypass. “This feature prevents the compressors from overheating when the highest water temperatures are required. It ensures reliable operation and an optimum service life,” says Van de Groep. “With the high-temperature heat pumps, we have delivered a sustainable solution that provides maximum comfort at minimum energy cost. We worked very closely with the installer to provide a suitable solution for the property owner. The multi-tenant office building is a fine example of how the transition from gas to heat pumps can be successfully implemented in existing buildings.” 

Een zakelijke vraag aan Airview Luchtbehandeling BV? Get in touch

Companies in this story

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ThemeGas-free heating and cooling
  • SubjectGeneral
  • CompanyAirview Luchtbehandeling BV
Share this article

Follow Installatie & Bouw Nederland

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.