Heat recovery in balanced ventilation

Since the European Ecodesign product legislation (ErP) came into force in 2016, heat recovery has been mandatory in balanced ventilation systems. Under the EPBD directives for existing buildings, heat recovery is a recognised measure that may or must be applied to achieve the required energy label in 2023. What options are available? What should you look out for? And is cooling recovery also possible, now that summers are getting warmer?
Since 2016, the ErP legislation (2014/1253) has imposed strict requirements on heat recovery in a balanced ventilation system (TVE). In particular, the required efficiency for run-around coils and plate heat exchangers has risen sharply, to 68 and 73% dry efficiency respectively. Dry efficiency is measured in laboratory conditions, without condensation in the extract air, and adjusted to equal air volumes based on the supply air volume.
Sensible efficiency measured in real-world conditions, with condensation in the extract air, can be 5 to 10% higher than dry efficiency. One direct consequence of this efficiency requirement is a significantly increased risk of freezing on the extract-air side in systems without moisture transfer. This process starts when supply air temperatures fall below zero and must therefore be prevented. As freezing begins, resistance increases, reducing the volume of warm extract air passing through and accelerating the freezing process. Experience shows that the unit can freeze up completely and become damaged within 10 to 15 minutes. The best protection against freezing is to measure the pressure drop in the extract air across the unit. Together with the measured extract air volume, this makes it possible to calculate the initial pressure rise caused by freezing. To prevent further freezing, the control system must reduce heat recovery efficiency, for example by opening the bypass damper or reducing the glycol pump output. The consequence of this necessary protection is that, in frost conditions, efficiency in systems without moisture recovery must be reduced from 73 to 60%, and sometimes to below 50%, depending on the indoor relative humidity (RH). The installation design often accounts for this by specifying a larger heater in the air handling unit and greater heating capacity to supply it. The difference compared with a system that does recover moisture can be as much as approx. 100%: at -10°C, the dT across the reheater is approx. 15°C rather than 7.5°C.

Low-profile heat wheel section.
European legislation performance requirements
The European Union’s ErP legislation sets strict efficiency requirements to deliver energy savings. However, these must not lead to disproportionate energy consumption. For this reason, the increase in fan power input is limited under 2014/1253. Fan power increases because of the additional air resistance caused by heat recovery and the necessary filtration of extract air. The total fan power for supply and extract under ErP is expressed as ‘internal Specific Fan Power’, or SFPint, in W/(m³/s). In the Netherlands, heating an outdoor air flow rate of 1 m³/s to 21°C for a full year (8,760 hours) requires approx. 125,000 kWhth/a of heat (heat absorbed by the air, excluding generation losses). Given the required heat recovery efficiency of approx. 70%, this means that a maximum of approx. 88,000 kWhth/a can be recovered each year. The SFPint for a run-around coil system includes around 1,000 W/(m³/s) to overcome resistance losses in the heat recovery coils and the extract air filter. This brings the electrical energy required for heat recovery to 8,760 kWhe/a. In terms of energy savings, the ErP performance requirement for a run-around coil system could therefore be compared with a heat generator with a COP of approx. 10. For systems with a plate heat exchanger or heat wheel, the maximum SFPint is considerably lower, giving these systems a comparable COP of approx. 15. This shows that the requirements for heat recovery in the ErP legislation are very reasonable: generation systems using waste heat, solar heat or geothermal heat consume less energy for a comparable amount of heat. Heat recovery is, of course, never the same as heat generation, because a building must first be heated by a heat generator before heat can be recovered from the extract air.
Compare heat recovery systems
In Dutch commercial building projects, heat recovery is achieved using heat wheels in approx. 75% of cases. Plate heat exchangers account for 15 to 20%, while around 5 to 10% use run-around coil systems. Balanced ventilation in homes is overwhelmingly provided by plate heat exchangers.
Run-around coils are generally used when it is not possible, or safe, to bring the supply and extract air together physically in one place. In a few cases, the air volume of a single air handling unit is so large that the space can only accommodate a run-around coil system. A pipe system filled with glycol connects the coil in the extract air handling unit to the coil in the supply air handling unit. When the connection is one-to-one, this is called a run-around coil. If several extract air handling units are connected to one or more supply air handling units, the system is called a multi-coil system. Heat recovery efficiency can be controlled using the pump in the glycol system. Pumping less glycol reduces the amount of heat recovered. A run-around coil system is effectively the only system that allows complete separation of the extract and supply air. This is not possible with either
a plate heat exchanger (leakage <0.25%) or a heat wheel (leakage <2%). With these systems, it is important to position the fans so that any leakage flows from the supply air to the extract air.
Both cross-flow and counter-flow plate heat exchangers are generally found in smaller air handling units. Cross-flow plate heat exchangers are manufactured with a maximum face size of 1.4 by 1.4 m, suitable for approx. 10,000 m³/h. At higher air volumes, multiple blocks are used. The photograph also shows a cross-flow heat exchanger handling approx. 30,000 m³/h, made up of 8 blocks. Because of the size of the assembled unit, the air handling unit is around 2 m longer than one with a heat wheel for the same air volume. As a result, the production costs of an air handling unit with a
large plate heat exchanger are relatively high. Air handling units with a single plate heat exchanger handling up to around 8,000 m³/h are no longer, and are sometimes even shorter, making them cheaper than an air handling unit with a heat wheel.
Efficiency is generally controlled using damper banks to prevent freezing in winter and overheating in summer. A bypass damper diverts the supply air around the heat exchanger. Rooftop air handling units are sometimes fitted with plate heat exchangers installed at an angle, with the supply and extract sections positioned side by side to limit the height of the unit. When choosing a cross-flow heat exchanger, the air streams will always cross. This must be taken into account when designing the duct connections. Air handling units must always be lifted and transported with care. Excessive movement during transport can sometimes open the joints between the plate heat exchanger and the walls of the air handling unit, resulting in unexpected additional leakage.
Relative humidity (RH)
Plate heat exchangers and run-around coils are also known as recuperative heat recovery systems, because they recover heat only. Moisture in the extract air condenses and must be discharged to the sewer. A droplet eliminator is often also needed downstream of the heat recovery unit in the extract air stream to capture any condensate droplets.
If the supply air is heated but not humidified, the building will become very dry in winter. In frosty conditions, the indoor RH is very likely to fall below the minimum value of 30%. Infiltration also contributes to lower RH in winter. Occupancy density and the presence of green plants, if any, increase RH in turn. Air that is too dry is unhealthy: throat, nose and eye complaints are the most common comfort issue. Electronic equipment can also fail because of dry indoor air (static electricity). A safe and healthy RH is between 40 and 60%. In recent years, various energy-saving programmes have pushed RH limits further, with all the associated risks. Humidifying ventilation air requires energy: a continuous flow of 1 m³/s (8,760 h/a) takes up around 37,500 l/a of water to reach an RH of 40%. For an RH of 50%, this rises to 73,500 l/a. The latent heat of evaporation alone, excluding generation efficiency, amounts to around 26,000 kWh/a and 51,000 kWh/a respectively. Compared with the heat required for any reheating, which is still 37,000 kWh/a per 1 m³/s (125,000 − 88,000), humidification energy certainly contributes to energy consumption.
Heat wheels
Heat wheels were invented 30 years ago as a healthy and sustainable ventilation solution. At the recommendation of the then College voor Ziekenhuisvoorzieningen (CvZ), they were widely installed in Dutch hospitals. Heat wheels allow water vapour to be transferred safely and efficiently. In winter, moisture is transferred from the extract air to the supply air, reducing humidification capacity and energy requirements. In summer, moisture is transferred from the outdoor air to the extract air, reducing cooling capacity requirements.
Heat recovery with moisture recovery is known as regenerative heat recovery. In any situation where healthy design requirements for indoor relative humidity apply, it is worth considering installing a sorption wheel in the air handling unit. A heat wheel is not recommended if the extract air contains odorous substances that must not be transferred to the supply air. If the air volume from, for example, toilets accounts for less than 5% of the total extract air volume, the standardised dilution is so great that a heat wheel can be used after all. Although there have been no identifiable cases of cross-infection via a heat wheel in the past 30 years, CvZ advised against installing heat wheels directly in operating theatres.
Modern sorption wheels use zeolite as the adsorbent material. Zeolite has a nanoporous structure. This means that its pores are only 0.3 nm wide, allowing only water vapour molecules (0.27 nm) to enter and adhere to the surface. A purge section flushes the air in the wheel back towards the extract air before it rotates further into the supply section of the air handling unit. Depending on the installation, a sorption wheel can reduce humidification capacity and energy requirements by 50 to 75%.
Thanks to the transfer of moisture, a sorption wheel will not freeze in winter, allowing the design heating capacity of the air handling unit to be 50% lower than with a plate heat exchanger or twin-coil system. The moisture transfer provided by a sorption wheel can also reduce the design cooling capacity of the air handling unit by up to around 40% in summer. Using sorption wheels significantly reduces the risk of low relative humidity, for example in offices without humidification.
Heat wheels can be manufactured with diameters of up to 5 m, suitable for an airflow of around 100,000 m³/h. High air volumes can be handled in shorter air handling units by installing two or more smaller heat wheels side by side. This solution, combined with modern EC fan walls, enables heat-wheel air handling units to be built in compact and relatively low configurations. The heat recovery efficiency of a heat wheel is determined by its rotational speed, which can be controlled by a V-belt around the wheel and a variable-speed motor. To prevent imbalance, the wheel operates in pulse-and-pause mode rather than stopping completely. In addition to the widely used sorption wheels, enthalpy wheels and condensation wheels are also available for more specific applications or as an intermediate option in terms of price and performance. An enthalpy wheel behaves much like a sorption wheel in winter, but transfers little moisture in summer. A condensation wheel behaves identically to a twin-coil system and a plate heat exchanger. The rotor’s aluminium surface has no adsorptive coating, so moisture in the extract air simply condenses. Like a twin-coil system and a plate heat exchanger, a condensation rotor can freeze over in winter.

Fan wall with EC fans.
Internal leakage in heat recovery
As mentioned earlier, only a twin-coil system with separate extract units is completely leak-tight. Both plate heat exchangers and heat wheels can leak air from the extract side to the supply side. Leakage across a heat recovery component depends not only on its quality, but also on the pressure difference across it. If the pressure on the supply side is higher than on the extract side, leakage will flow predominantly from supply to extract. The reverse also applies. The position of the fans is important here. In the Netherlands, air handling units with heat recovery are commonly designed in two different configurations. In the first, the extract fan is positioned on the outdoor-air side; in the second, it is positioned on the building side. The second configuration is needed when the building also uses recirculation. For example, buildings with induction units often use recirculation during operating hours to warm the building. This configuration also usually results in a shorter unit and therefore takes up less space, which can be another reason for choosing this design.
In the second configuration, positive pressure on the extract side of the heat recovery section and negative pressure on the supply side result in relatively greater leakage from extract to supply. This applies to both plate heat exchangers and heat wheels, but the leakage is usually greatest with a heat wheel. Eurovent has been focusing for some time on internal leakage in air handling units, as it affects energy consumption and supply-air quality. It is investigating whether internal leakage could also be included as a Eurovent quality parameter in the Eurovent certificate.
Heat wheels in large buildings
Large buildings such as (academic) hospitals often contain many internal rooms. An internal room does not adjoin the façade, so it has lower or no heat losses in winter. These buildings are often designed from an HVAC perspective with an all-air system and post-heating. In summer, they are cooled directly using ventilation air (all-air), while in winter the relatively cool central supply air from the air handling units is often post-heated in each room. The central supply-air temperature is set so that internal rooms can be cooled in winter if required to offset internal heat gains.
Large buildings are often humidified using steam. However, adiabatic humidification can be used instead. Adiabatic humidification cools the supply air as it absorbs moisture. This is particularly beneficial in large buildings where the central supply-air temperature is considerably lower than the room temperature. There is little need to limit humidification, and a large proportion of the energy used for humidification is supplied by the additional recovered heat. This considerably increases annual temperature and humidity efficiencies. The savings compared with steam are proportionally even greater, since water does not need to be heated to 100°C for adiabatic humidification. Unlike older water humidifiers, the air handling unit dries out completely when humidification is not required, and humidification uses very pure ‘reverse osmosis water’. This provides a safe humidification method that reduces the additional energy required on the demand side alone from around 60 to around 23%.
New, safe methods of adiabatic humidification are now available. Depending on the situation, the choice can be evaporation, atomisation or a hybrid combination of the two. Experience shows that, in the example described, with a relatively low central supply-air temperature, installing modern adiabatic humidification in new air handling units has a payback period of well under 5 years. Retrofitting existing air handling units to replace steam with adiabatic humidification also often pays back in less than 10 years, making it one of the recognised measures for improving the energy label to at least C in 2023.