Old and new come together at Museum Abby

One of the museum’s guiding principles is: sustainable and fair, making an impact on people, not the environment. With this statement in mind, the museum began its renovation and refurbishment works. The project took 2.5 years in total, but the result is now there for all to see. Museum Abby has become an impressive and striking building. From the outside, its modern pyramid-like form stands out most. Once inside, its red colour and high ceilings make it even more impressive.
The museum comprises both old and new buildings. As well as renovating the existing buildings, the museum was expanded with a new pavilion and underground exhibition spaces. The buildings had to be connected, which made the installation considerably more complex due to the large amount of pipework required.
The second challenge was climate control in the museum. To keep the vulnerable artworks in optimal condition, a stable and reliable ambient temperature and humidity level are essential.


Hybrid 4-pipe heat pump system
A hybrid 4-pipe heat pump system was eventually chosen. The Enevator Air Standard 4-pipe heat pump has a heating capacity of 185kW and a cooling capacity of 174kW. The advantage of a 4-pipe heat pump system is that it has independent circuits, allowing it to heat or cool separately, or to heat and cool simultaneously.
For this project, the 4-pipe system provides both underfloor heating and cooling, supplying the various climate zones with heat or cooling. This ensures that the museum always maintains the right temperature and humidity. Keeping temperature and humidity at a constant level is particularly important for the museum to preserve its art collection. This means that both heating and cooling are required throughout the year, making a 4-pipe system the ideal solution for redistributing energy efficiently.
The system also supplies the booster heat pump, which produces domestic hot water for the buildings. A condensing gas boiler is also integrated to provide additional heating on the coldest winter days.
A hybrid system was chosen deliberately. The 4-pipe system was designed to create a perfect balance between the heat extracted from and released into the building. This ensures sustainable and efficient climate control.


Our installation included:
- Enevator Air Standard AWHS 270 ACF/SLN/RV/4P heat pump
- SBT 2,000-litre buffer tank for cooling
- Enevator Aqua Booster WWHB 20
- Plate heat exchanger
Condensing gas boiler as backup
COP stands for Coefficient of Performance. It is the ratio of the thermal energy produced by the heat pump to the total electrical energy it consumes. A heat pump’s efficiency decreases as the outdoor temperature drops, meaning its COP falls. Depending on gas and electricity prices, there is a certain break-even point at which it may be worth using a gas boiler alongside the heat pump. This may be the case, for example, when outdoor temperatures fall below 0 degrees. At extreme temperatures below -20 degrees, it may be better to switch off some heat pumps to prevent them from freezing. A backup is then needed to guarantee 100% operational availability. In this case, 100% operational availability was one of the museum’s requirements, ensuring that the artworks remain in good condition even during severe winters.
Would you like to know more about the differences between 2-pipe and 4-pipe heat pump systems and how they are used? Request the guide here and receive a free download in your inbox.
Do you also have a climate control and/or domestic hot water project underway and need advice? Contact our expert Wim Ros.
A business enquiry for Performance iN Lighting? Get in touch
Companies in this story
Keep following this
Get an email when a new story is published. No account needed.
- ProjectMuseum Abby
- SubjectGeneral
- CompanyPerformance iN Lighting