Are pv panel dc connectors a fire hazard?

There is considerable debate about the correct use of DC connectors on PV panels. Several fires have been linked to faulty DC connectors. Most faults are caused by incorrect installation or the use of unsuitable products. NEN1010 sets out fairly clear requirements for using connectors from different manufacturers. InstallatieJournaal covered this topic in December 2018, and I would like to offer some additional insight here.
PREVENT FIRES AT PV DC CONNECTORS: 5 TIPS FROM JOOST
Only combine two compatible brands!
In short, connectors can be used together if both manufacturers state that they are compatible, or that connectors from different manufacturers can be safely combined. If either manufacturer does not confirm this, connectors from the two brands must not be connected to each other. Doing so creates safety risks and increases the risk of fire.
The main reason for the NEN1010 requirement is that the MC4 connector from MultiContact (manufacturer Stäubli) is not a standardised product. MultiContact’s MC4 connector is a proprietary product. As it is not standardised, there are no exact, publicly available product specifications that the connector must meet.
This means we can never be certain that manufacturers who have
“copied” the product have used exactly the same materials or dimensions. As a result, we can never be 100% certain that a connection between connectors from two brands will continue to work properly throughout its expected service life.
So, to reiterate, only connect connectors from two different brands if both manufacturers have confirmed that it is safe to do so. The fact that many fires have already been caused by faulty connectors underlines the importance of understanding this provision in NEN1010.
How do fires start?
DC connectors should not be placed directly on the roof covering or on sloping roofs. This YouTube video clearly shows what can happen.
But what exactly happens? The problem is that cable glands are never completely watertight. The connector’s cable gland must be tightened properly, and the connector must also be fully mated. There is always some air inside the connector. When the connector is placed directly on the roof, the sun warms it up, heating the air inside too. This increases the pressure in the connector, which can force air out past the cable gland. In the evening, the connector cools down again, creating negative pressure inside it. This can draw cold, moist air into the connector, causing corrosion at the electrical connection. Over time, this causes contact resistance, followed by overheating, which can then lead to fire.
5 tips for connecting the connectors
Use compatible connectors only.
For the reasons outlined above, it is important to use compatible connectors only. The solar panel manufacturer may also supply loose connectors for use in the installation. Remember that you must also check the connector that connects to the inverter. Fortunately, some inverter manufacturers supply the correct connectors too.
Use the right tools.
The most important tip is to use the right tool to crimp a connector. Combination pliers and water pump pliers are not suitable for making a proper connection. Use the tool specified by the connector manufacturer.
Cut off the last connector in the string.
Avoid mixing brands by cutting off the last connector in a string of solar panels and crimping on the correct one. The correct connector means the “male” and “female” connectors from the same manufacturer. This assumes that all the other connectors in the string are from the same connector manufacturer.
Use good cable management.
Never place DC connectors directly on the roof covering or on a sloping roof. Make sure the wiring and connectors are secured in a cable tray or wire-mesh tray. More generally, secure the wiring and connectors to the supporting structure in a location where as little water as possible runs past them.
Install carefully.
Carefully tightening the cable gland reduces the risk of moisture getting into the connector. Also make sure the connector is fully mated. This too reduces the risk of water entering the connector and therefore the risk of fire. Finally, make sure cable ties are not too close to the connector. This prevents the DC cable from sitting at an angle in the cable gland, which would increase the risk of water ingress.