‘The move to lower-GWP refrigerants brings new challenges’

In 2015, legislation was introduced requiring the use of synthetic F-gas refrigerants with high GWP values to be reduced in both existing and new HVAC systems. A reduction schedule was set, from 100% in 2015 to 21% in 2030. The reduction was measured in ‘tonnes of CO2 equivalent’ for the refrigerant concerned, also known as its GWP (Global Warming Potential).
Take the refrigerant R410A as an example. It has a GWP of 2088, which means that each kilogram of this refrigerant produced or imported counts as 2088 towards the reduction target. The widely used refrigerant R32 has a GWP of 675, meaning that the reduction schedule allows three times as much R32 to be used as R410A.
By 2022, the reduction target had reached 45%, with just 8 years remaining until the 21% target for 2030. In addition, the current reduction targets were reviewed in mid-2022, and a proposal was put forward to accelerate the reduction further, to 5.17% in 2030 instead of 21%. This makes it necessary to use refrigerants with even lower or very low GWP values. But this has significant implications for installers, consultants and end users.
The refrigerants currently available as replacements for HVAC systems with hermetically sealed systems include R32 (GWP 675), R454B (GWP 467) and R290 (GWP 3). Replacements available and suitable for HVAC systems with semi-hermetic systems include R513A (GWP 631) and R1234ze (GWP <1). But there is a catch, or rather, ‘a new challenge is emerging’. The lower the GWP of the alternative refrigerant, the more flammable it is. R32, R454B and R1234ze are classified as ‘mildly flammable’, while R290 is classified as ‘highly flammable’.
To continue manufacturing and installing HVAC systems while meeting the stricter reduction targets, we have to turn to refrigerants that are no longer non-flammable. There is no avoiding this, and it can have a major impact on the design, construction and maintenance of these systems. The recently revised EN 378 provides guidance on good design and includes an ANNEX C for determining charge limits based on toxicity and flammability. The old NPR7600:2013 provided guidance only for hydrocarbons such as R290. The new NPR7600:2020 provides guidance for all flammable refrigerants, including R32, R454B and R1234ze as well as R290.
The key message, then, is to familiarise yourself with this guidance now, so that you know the maximum refrigerant charges, any additional safety measures required, and whether there are potentially explosive zones around an installed unit. Start training service technicians now so they are ready to maintain these systems.