Dancing until daylight
Text Lieke BousemaImage Airco HP

New air handling system at Nachtclub Escape improves comfort and cuts energy use
Nachtclub Escape on Rembrandtplein in Amsterdam has recently been fitted with a new air handling system, giving visitors greater comfort while significantly reducing energy consumption. Airco HP carried out both the engineering and replacement work, and selected Systemair to supply the air handling units.

“The air handling units at Nachtclub Escape dated back to 1986 and had reached the end of their technical life,” says Jasper van den Heuvel, owner of Airco HP. “The nightclub owner therefore asked us to draw up a replacement proposal that took sustainability and energy efficiency into account, and would also allow fresh outside air to be pre-treated, with cooling and heating. We carried out a baseline assessment of the existing installation on site. We also mapped the client’s requirements, the building’s technical capabilities and the site constraints, which provided the basis for the engineering work.” Systemair was brought on board early in the process. “We approached three suppliers to submit proposals for the new air handling units,” says Patrick van de Brug, Ventilation Technology, Air Conditioning and Heat Pump Specialist at Airco HP. “Systemair was the only supplier able to provide units that met both the client’s requirements and our own vision.”

Limited space
“Airco HP approached us in November 2022 to develop a replacement proposal incorporating heat recovery,” says Ron Gijsbertsen, Account Manager at Systemair. “Together with Jasper and Patrick, I assessed the existing situation, requirements and constraints. The limited space on the roof in particular presented challenges. We also had to take a neighbouring home into account. On my advice, for example, the largest air handling unit was installed rotated relative to its predecessor, reducing the amount of rooftop ductwork required. This also reduces noise transmission to neighbouring buildings.”
Ventilation using negative pressure
Systemair recommended and supplied a total of four Geniox air handling units: one 28,500 m3/h supply unit, two 17,000 m3/h supply units and one 26,000 m/h extract unit. “The supply units are fitted with filters that remove fine particulate matter and other contaminants from the incoming outside air,” says Gijsbertsen. “The air is then pre-treated by the fan and DX coil before being supplied to the rooms. The extract unit draws in used indoor air and discharges it outside, creating negative pressure in the rooms. This automatically draws in enough conditioned fresh air.”

Significant energy savings
All Geniox units feature an energy-efficient fan (0-10 Volt), which can be controlled as required based on CO2 levels, room temperatures or a timer. “With a dedicated control system, CO2 and temperature sensors, fresh outside air can be pre-treated in response to demand,” says Gijsbertsen. “Timer programmes are also available.” Van de Brug adds: “The owner of Escape has chosen to manage the air handling units in-house, switching them on, adjusting them and switching them off depending on how busy the nightclub is. This can save a lot of energy.” All the units use R32 refrigerant, which has a relatively low Global Warming Potential (675).
Tight schedule, challenging logistics
A condition of the project was that the work had to be carried out between Sunday night and Thursday afternoon, so the nightclub could stay open on peak days, says Van de Brug. “To make this possible, as much of the existing ductwork in the nightclub as possible was retained. Fortunately, the existing ductwork proved adequate for the new installation to operate properly.” Given the site’s location on Rembrandtplein, all the existing air handling units had to be removed and all the new units installed in a single lifting operation. “We started the lifting work at 0:30 and had to pull out all the stops to finish by 6:00,” says Van den Heuvel. “We were not allowed to bring all the units into the city in one go, so we drew up a careful transport plan in consultation with our lifting partner Modern Berging. During the preparatory phase, our installation team ensured that all the existing systems had been pumped down on the refrigerant side. Electrical partner RDM Techniek had also prepared all the power supplies for the new installation in advance. This meant that as soon as the units had been positioned and connected to the ductwork, we could complete the electrical connections straight away.” As the new system uses conditioned air, Meurs Isolatie en Montage insulated and finished the rooftop ductwork. To keep the project moving quickly, Airco HP worked in shifts. Mitsubishi Heavy Industries air-to-air heat pumps are connected to each supply unit.
In September, Airco HP and Systemair jointly commissioned the system, with Systemair’s engineers setting all the parameters, from temperatures to airflow rates.
A business enquiry for Systemair? Get in touch
Who worked on it
Nachtclub Escape in Amsterdam
- Geniox luchtbehandelingsunits
Systemair - air-to-air heat pumpsMitsubishi Heavy Industries
- elektropartnerRDM Techniek
- hijspartnerModern Berging
Keep following this
Get an email when a new story is published. No account needed.
- ProjectNachtclub Escape
- ThemeHealthy indoor air
- SubjectHVAC
- CompanySystemair
- CompanyMitsubishi Heavy Industries
- CompanyRDM Techniek
- CompanyModern Berging