Danone new-build, Hoofddorp | Danone new-build focuses on health and sustainability

A state-of-the-art office building with a strong focus on sustainability, health and a comfortable working environment. That is the best way to describe Danone’s new building at Beukenhorst-Zuid business park in Hoofddorp. Commissioned by developer Red Company, the project includes a two-storey car park, four office floors and a large glazed atrium, embracing Danone’s ‘One Planet, One Health’ philosophy. The mechanical and electrical services make a major contribution to this.

All the air handling units for Danone were supplied prefabricated, including the controls.
Danone’s new building was designed by architecture practice Powerhouse Company. DVP is responsible for overall project management and Pleijsier Bouw is delivering the construction, while Roodenburg Groep is responsible for all building services. “In accordance with the building services design by Deerns and the WELL Gold (health) and LEED Gold (sustainability) certification criteria, we installed a thermal energy storage system with four boreholes and a heat pump system,” says Arno Schrader, Project Leader at Roodenburg Groep. “Two boreholes are allocated to Danone’s head office. The remaining boreholes provide the base heating and cooling for the adjacent ASICS new-build, for which we recently also installed the mechanical, electrical, sprinkler and sanitary systems.”
Danone’s new head office will be climate-controlled using climate ceilings, combined with base-level air heating and cooling, Schrader explains. “In the summer, air at a standard temperature of 18°C is supplied to the offices; in winter, this rises to 21°C. Employees who wish to can easily adjust the temperature by up to three degrees either way using an app on their smartphone. This ensures an optimal working climate. Convectors along the glazed façades prevent discomfort caused by cold downdraughts.”
An electric boiler has been connected to the thermal energy storage system to meet any peak heating demand. A dry cooler keeps the boreholes in balance, Schrader explains. “The dry cooler is on the roof of the head office, alongside a heat recovery unit and four air handling units.” Roodenburg Groep called on Systemair to engineer, prefabricate and supply the air handling units. “Systemair’s units proved to be better than those of other suppliers, both in quality and technical terms. What’s more, Systemair’s account managers worked with us to find smart solutions and stayed within our budget.”
Energy label A
“All the air handling units in this project had to achieve energy label A,” says Sjef Verboven, Account Manager at Systemair. “We met this requirement for the offices with two identical units rated at 22,000 m³/h, fitted with energy-efficient EC motors (efficiency class IE4) and rotary heat exchangers. The selection for the restaurant and kitchen was a little more difficult. Rotary heat exchangers are not recommended here because of the risk of odour transfer. Cross-flow heat exchangers are an alternative, but at a minimum efficiency of around 75% they usually have high air resistance. This is penalised in the energy label calculation. One solution is to specify slightly larger air handling units. As the units for the restaurant and kitchen in this project were not particularly large, at 12,000 and 9,000 m³/h, this oversizing quickly achieved the desired result.”
The dimensions of the air handling units presented a greater challenge, he says. “Because the new building is close to the airport, a maximum building height was specified. To meet the requirements, our air handling units could be no higher than 2,500 mm. This was particularly challenging for the office units. We configured these units as so-called ‘monoblocks’, a design without an intermediate frame but with an integrated intermediate floor. The result was a neat 2,498 mm.”
Ready-to-install units
All the air handling units for Danone were supplied prefabricated, including the controls, Verboven explains. “On the roof, all that remains is to connect the heating, cooling and polyester air ducts. The control panel and all the cabling were fitted at our factory.” To ensure a clear demarcation between the hardware and software, Systemair took responsibility for all the cabling and equipment inside the units, from the servomotors and sensors to the fans and lighting. The control panels were developed in collaboration with Roodenburg Groep, including the controller and main switch. In week 49, all the air handling units were transported to Hoofddorp and placed on the roof, where Roodenburg Groep is completing the remaining connections.
A business enquiry for Systemair? Get in touch
Who worked on it
Danone headquarters Hoofddorp in Haarlemmermeer
- air handling units
Systemair - developerRed Company
- architectural practicePowerhouse Company
- overall projectmanagementDVP
- constructionPleijsier Bouw
- complete installatietechniekRoodenburg Groep
- installatietechnische ontwerpDeerns