HVAC

Heat pumps contribute to an energy-efficient and comfortable indoor climate in MercachemSyncom’s new wing

Heat pumps contribute to an energy-efficient and comfortable indoor climate in MercachemSyncom’s new wing

The construction of a new wing at MercachemSyncom’s KKB1 headquarters in Nijmegen in 2018 has given the chemical laboratory enough room to grow again. It has also created a new workplace for around 40 employees, who had previously carried out their synthesis work at a branch on the university campus in Nijmegen. The new KKB2 building includes laboratory spaces, offices and meeting rooms, warehouse, storage and archive areas, a reception area, passenger and goods lifts, and a link bridge to the existing building. Both KKB1 and KKB2 were designed by Adviesbureau Becks, which was responsible for the building services installations. Its work covered everything from design through to tendering and permit applications, as well as project management during construction. 

The new KKB2 building includes laboratory spaces, offices and meeting rooms, warehouse, storage and archive areas, a reception area, passenger and goods lifts, and a link bridge to the existing building.

MercachemSyncom is a Dutch Contract Research Organisation. Drawing on its expertise in chemistry, it supports pharmaceutical and biotechnology companies worldwide in their search for new medicines. “A perfect balance of design, ergonomics and indoor climate is essential,” says Bart van den Heuvel, Engineer at Adviesbureau Becks. “To achieve this, we worked closely with MercachemSyncom to review and update the client’s brief for the new building, drawing on experience from the existing building. Particular attention was paid to integrating the fume cupboards into the ventilation system. There were also specific requirements for humidity, temperature, noise and comfort. Maintaining a suitable pressure hierarchy was essential to prevent contamination in the laboratory spaces.”

All laboratory spaces are maintained at negative pressure 24/7, with more air extracted than supplied, he says. “As the fume cupboards have a significant impact on the air balance when opened and closed, ventilation and humidification are fully demand-controlled.”

Western Airconditioning’s 4-pipe heat pump system can provide cooling and heating simultaneously.

Simultaneous cooling and heating

In addition to the client’s brief, Adviesbureau Becks carried out a spatial survey, documenting the use of each room and its associated internal heat load, airflow rates and other factors. “This survey showed, among other things, that processes and equipment in the laboratories generate a high heat load, reaching as much as 470 W/m² in one particular lab, much of which needs to be removed. This is also the case in winter, when the offices have a heating demand. To meet this need, we looked for a plant system that could transfer this energy. The solution was Western Airconditioning’s 4-pipe heat pump system, which can provide cooling and heating simultaneously.” Western Airconditioning actively contributed to fine-tuning the system for this project. It was specified by Adviesbureau Becks and awarded the contract to supply a 4-pipe air-to-water heat pump. The company, based in Hoevelaken, also supplied a 2-pipe air-to-water heat pump, which can provide energy-efficient heating or cooling.

Optimum energy efficiency

In addition to the climate conditions, energy consumption was subject to stringent requirements, says Van den Heuvel. “Our design objective was not simply to reject the heat generated in the laboratories into the outside air, but to recover it sustainably. Some of the air is therefore extracted and exchanged via the air handling units, while the rest is used by the 4-pipe heat pump. The result is optimum energy efficiency.” 

The 4-pipe air-to-water heat pump has a cooling capacity of 105 kW in summer and a heating capacity of 107 kW in winter, says François van Gorkom, Account Manager at Western Airconditioning. “The heat pump is highly efficient, with an EER of 3.5 for cooling and a COP of 3.9 for heating. The highest efficiency, however, is achieved when the heat released during cooling is transferred to the hot-water circuit. This delivers a TER of 7.62.” Both heat pumps are connected to hot and cold buffer tanks. Circulation pumps provide demand-controlled delivery of heating and cooling to the terminal systems.

Installation of the heat pump system.

Heating continues without interruption

“Both the 4-pipe and 2-pipe heat pumps have two separate refrigerant circuits, which not only reduce the refrigerant charge per circuit but also ensure optimum reliability,” says Van Gorkom. “The refrigerant circuits operate independently of one another. In winter, only one circuit at a time can enter the defrost cycle, so heat can always continue to be supplied to the system. The heating process is therefore never interrupted.” The heat pumps also have very low start-up currents and minimal electricity consumption. This was a key benefit, according to Van Gorkom and Van den Heuvel, because the electricity supply from the utility company was limited.

The new building has now been in use for a year. Adviesbureau Becks carefully monitors all building services installations and optimises them where necessary, to ensure that MercachemSyncom receives what it was promised at the outset.   

Question about this story? Ask your question

Who worked on it

KKB2 in Nijmegen, new build

  1. warmtepompsysteemWestern Airconditioning

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ProjectKKB2
  • ThemeGas-free heating and cooling
  • SubjectHVAC
  • CompanyWestern Airconditioning
Share this article

Follow Installatie & Bouw Nederland

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.