Keep your extraction system in top condition!

Keep your extraction system in top condition!

Specialists in cleaning, renovating, overhauling and reconditioning climate control systems, Conpro Condensor Bescherming BV regularly carries out maintenance work at a large number of internationally renowned restaurants. This work is undertaken both directly for franchisees and on behalf of installation contractors.

Maintaining air handling systems is crucial, especially in commercial kitchens

“In 2016, on behalf of Hamer BV in Apeldoorn, we chemically and technically cleaned the air handling unit serving the kitchen of a restaurant alongside the A15”, says Jens Groenendijk, account manager at Conpro Condensor Bescherming BV. “During the cleaning process, we sprayed the blackened, baked-on grease deposits in the air handling unit with a special Conpro gel. The gel bonds to the grease, gradually loosening it. We then used a special manual scraping and brushing technique, together with a steam cleaner, to remove all the grease and gel residue from the system and dispose of it, leaving the system clean.”

Deteriorating condition

The work was carried out to the great satisfaction of all parties, Groenendijk says. However, in 2019 the restaurant manager noticed that extraction capacity in the kitchen was again declining during peak periods. “Hamer BV then inspected the complete extraction system and carried out a technical air measurement on the air handling unit, which showed that the resistance across the cross-flow heat exchanger was too high. We were therefore contacted again to carry out a chemical and technical clean. We completed the work in June 2019, after which a new air measurement was taken. This showed a significant improvement, but the system had still not reached its original design conditions. It remained in operation for some time, until the restaurant manager raised the alarm again in November 2019: the system’s condition was deteriorating rapidly once more. This gave Hamer BV and Conpro Condensor Bescherming BV sufficient reason to replace the cross-flow heat exchanger.”

20200121_031202-kopieren

Installing the new cross-flow heat exchanger.

Excessive resistance caused by baked-on grease residue

The amount of grease and oil released in the restaurant kitchen had caused the cross-flow heat exchanger to become blocked. Unfortunately, it could no longer be repaired, Groenendijk says. “Rather than having a chemical and technical clean every two years, the system in Tiel should have been cleaned annually. This would have prevented the kitchen grease from not only building up in the cross-flow heat exchanger, but also hardening there. The grease residue could no longer be removed, and resistance across the heat exchanger had risen to such a level that the situation became untenable during peak periods. In mid-January, we replaced the cross-flow heat exchanger and oil collection filters. To provide a clean working environment, the air handling unit was also given another chemical and technical clean beforehand. A new air measurement confirms that the extraction system is now working as intended, and all the staff are very satisfied.”

To avoid disrupting the restaurant’s operations, all work was carried out between 01:00 and 06:00 in the morning.   

A business enquiry for Hamer? Get in touch

Companies in this story

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • SubjectHVAC
  • CompanyHamer
Share this article

Advertisement

Follow Installatie & Bouw Nederland

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.