New heat pumps increase efficiency by more than 70%

Since 2001, Handicare has used a water-to-water heat pump system combined with energy piles to provide climate control in its 9,000 m2 building. “The piles in this project serve not only as foundations, but are also used to extract heat and cold from the ground and store them,” says Marco Roemersma, director and owner of Roemersma Installatie & Advies B.V. “To make this possible, heat exchangers were installed in the piles during construction.” The heat is used for the building’s underfloor heating, while the cold is used in the summer months to cool the air in the air handling system. This keeps the heat pumps’ Delta T, meaning the difference between the flow and return temperatures, to a minimum.”
Sustainability is gaining momentum
Maximum efficiency
Roemersma has been the regular installer for Handicare and building owner Dream for many years, handling both mechanical and electrical installations. “When the heat pumps reached the end of their technical service life, I was asked to design a new system,” he says. “Handicare wanted a system with the highest possible efficiency, in line with its green ambitions. Another requirement was that it should incorporate a manufacturer-independent control system.”

Roemersma contacted long-standing partner Western Airconditioning to engineer and supply the heat pumps. “Together, we reviewed the installation’s key figures and design criteria,” says François van Gorkom, Account Manager at Western Airconditioning. “On that basis, we assessed which heat pumps would best suit Handicare’s operations and sustainability ambitions. We selected our BlueBox Tetris W OH 8.2 water-to-water heat pumps, each with a heating capacity of 79 kW and a seasonal coefficient of performance (SCOP) of 5.9, corresponding to energy class A+++. In summer, 64.1 kW is extracted from the ground for use in cooling the building.” The high-efficiency heat pumps deliver substantial energy savings, he says. “This directly reduces energy consumption and can also help improve the building’s energy rating. That is particularly valuable now that, from 2023, office buildings larger than 100 m2 must have at least a C rating.”
Additional system volume, new control system
A number of modifications were made to the existing installation to accommodate the heat pumps, Roemersma says. These included minor changes to the pipework. “By installing an additional buffer tank, we increased the system volume by 200 litres. We also added a completely new control system, which means we can now monitor and manage the installation remotely. Priva Blue ID makes it easy to adjust setpoints, allowing us to get even more efficiency from the heat pumps. The cascade configuration also contributes to this.”

The BlueBox Tetris W OH 8.2 heat pumps use R410A refrigerant, which is non-flammable and non-toxic. “Both heat pumps are equipped with two scroll compressors, enabling them to operate accurately and with high energy efficiency at part load,” says Van Gorkom. “A smaller circulation pump was also installed. Together with the control system and cascade configuration mentioned earlier, this ensures very high efficiency.”

Compact design
Western Airconditioning delivered the complete heat pumps to the project just in time, he says. “Roemersma Installatie & Advies B.V. then handled the internal logistics, installation on the existing structural plinths and all connections. As the heat pumps are less than < 800 mm wide, they could easily be transported through the building to the plant room.” The new installation was commissioned in early October 2021.