Preventing stagnation or thermal decoupling?

Detecting and preventing Legionella risks: Flow-through wall plates minimise stagnation in cold water and domestic hot water circulation systems, helping to ensure the required temperature is maintained right up to the final outlet.
Using wall-mounted mixer taps in combination with wall plates mounted on a wall bracket has a negative effect on temperature maintenance. With the domestic hot water circulation pipe at 60 °C, heat transfer to the cold water connection can cause the cold drinking water temperature to rise above the critical temperature of 25 °C. As a result, even if the system is designed in accordance with NEN 1006, the required temperature cannot always be maintained in practice. This creates a significant risk of Legionella contamination. Wall-mounted mixer taps themselves also pose a risk of microbial growth, as microorganisms can colonise the rough inner surface of the taps particularly easily.

Thermally decoupling the hot water outlets from the circulation system by using an uninsulated draw-off pipe of ≥ 1 metre would solve this problem. However, if water is not drawn off for an extended period, there is a significant risk of stagnation. Kemper has the solution: the KEMPER THERMOTRENNER combines thermal decoupling with stagnation prevention. By using a heat-dissipating section with minimal water content between the circulation pipe and the integrated wall plate, the temperature of the wall plate and the water is kept at the same level as the ambient temperature.