‘Raise the pH of the water in your systems to 9 to 10’

Tap water is pH-neutral and ideal for drinking. However, its quality makes it less suitable for use in heating, cooling and refrigeration systems. A low pH can lead to corrosion, fouling and reduced efficiency. To prevent these problems, the tap water in the system must be deoxygenated as quickly as possible.
During the so-called degassing process, the pH of the water rises, preventing limescale particles from dissolving. The released limescale particles settle on the bottom of the system, resulting in extensive sludge formation, a significant drop in efficiency, and faults and failures in valves, control valves, controllers, pumps and other components. “To prevent this, we encourage installers to fill heating, cooling and refrigeration systems only with water that has the correct lime content,” says M.G. van Gorsel, director of KOREX Benelux. “VUL-SEP® is ideal for this purpose. VUL-SEP® is an advanced filtration system containing a special resin, which can easily be installed between the tap and the heating, cooling or refrigeration system. Thanks to the water softener, only very soft water with a German hardness of 3 degrees (˚dH) is added to the system, significantly speeding up the preservation process. It also prevents problems caused by limescale deposits, resulting in greater efficiency and a longer service life for the system.”

AIR-SEP® consists of an expansion vessel with an inlet valve, air vent, automatic filling unit and pressure maintenance pump, which eliminate air bubbles from the pipework.
Compliant with VDI 2035
In general, the lower the temperature in heating, cooling and refrigeration systems, the more air can dissolve in the water. This neutralises the pH, Van Gorsel explains. “That is a major problem, particularly in low-temperature systems. It is no coincidence that Germany has a standard in force, VDI 2035, which is intended to prevent damage caused by limescale (calcium carbonate) forming on heating surfaces. The standard, which we hope will soon be adopted in the Netherlands, stipulates, among other things, that water in closed circuits must be colourless and odourless, free of sediment and have a conductivity of ≤ 1,500 μS, depending on the size of the system. The pH must be between 9 and 10, with a hardness of 3 ˚dH. Our AIR-SEP® process can ensure that the water meets all these requirements.”
AIR-SEP® consists of an expansion vessel with an inlet valve, air vent, automatic filling unit and pressure maintenance pump, which eliminate air bubbles from the pipework, he explains. “The pressure maintenance pump repeatedly draws between five and twenty litres from the system, then returns it to the AIR-SEP® vessel through the inlet valve. The pressure is reduced here to a vacuum pressure of -0.3 to -0.5 bar. Our patented vacuum technology ensures a reduction in air content of 28 to 40 mg/litre compared with the system water. This raises the pH, keeps the protective oxide layers in the system intact, and prevents air and dirt from being released into the system.” Continuous pressure monitoring keeps the system pressure in the AIR-SEP® at an optimum level. “Rather than degassing water at set intervals, the degassing interval and run time are adjusted to the current system status. A touchscreen on the AIR-SEP® provides 24/7 visibility of system status and reports any faults, so they can be rectified immediately.”

Small filter.
Ultra-powerful magnet
All AIR-SEP® units from KOREX Benelux are fitted with an ultra-powerful magnet, which helps dirt particles settle out more effectively and traps them in the so-called ‘dirt zone’. During the system’s annual maintenance, all dirt particles can easily be removed from the bottom, resulting in a clean system, fewer faults, optimum efficiency and maximum service life. A softening tube can also be added as an option. The softener and magnet are monitored by a fully integrated, freely programmable microprocessor control system, which also automatically controls and monitors pressure maintenance, venting, vacuum degassing, expansion, dirt collection, cleaning and refilling with vacuum-degassed water. An optional MODBUS/TCP interface enables remote management.
Water treatment can be taken a step further by connecting an RVS 316L DEEL-SEP® side-stream pump and filter housing with a filter cloth to the AIR-SEP®, with filtration ratings from 100 to 1 μm. The preferred arrangement is parallel to the main return pipe. The system pumps water through the filter and returns it to the return pipe after filtration. In practice, a side-stream capacity of around 10 per cent of the main return flow is sufficient for this purpose, depending on the system’s history, level of contamination and size.
Een zakelijke vraag aan KOREX Benelux? Get in touch
Companies in this story
Keep following this
Get an email when a new story is published. No account needed.
- ThemeFuture-proof water and sanitary systems
- SubjectBuilding services engineering