‘Together, we are working towards an optimal energy supply’

Development of Boskalis’s site in Papendrecht began around 20 years ago, and the campus has continued to grow alongside the company. Construction is now well under way on ‘Gebouw 6’, an office building that will provide space for 500 workstations. The design for the new building was created by OPL architecten. Visser & Smit Bouw B.V. was responsible for the building work, while HOMIJ Technische Installaties is installing the mechanical and electrical systems. Hager is supporting the Major Projects department, among other things, by engineering and supplying the main and sub-distribution boards, and designing, supplying and installing the busbar trunking system.
‘Gebouw 6’ is due for completion in mid-2020 and comprises a central building with 5 storeys and 3 perpendicular wings, each with 4 storeys. The energy supply is connected to the campus’s existing transformer building. “Two main distribution boards have been installed on the ground floor to distribute power to the various floors,” says Rober Mebius, Project Manager at HOMIJ Technische Installaties. “A third main distribution board has also been installed in the plant room on the fourth floor. Busbar trunking distributes power to the plant room. Cables and cable trays have been chosen for all other connections.”
The three main distribution boards and thirteen sub-distribution boards were engineered and supplied by Hager, which regularly works on projects with HOMIJ Technische Installaties. “The collaboration on this project is going well too,” says Mebius. “Communication is open and decision-making is quick. Hager is also flexible and works with us to engineer the best and most cost-effective products for the project. Connecting to the main and sub-distribution boards has gone smoothly, and the products are of excellent quality.”

The IP41 distribution boards with Unibar H busbar trunking connections.
From design through to production and delivery
“We designed the distribution boards based on HOMIJ Technische Installaties’ installation schematic,” says Martwin de Man, Project Manager at Hager. “The design complied exactly with the specified dimensions, short-circuit currents and protection ratings (IP41 for the main distribution boards). Once approved, we converted it into technical production drawings. The main distribution boards were built at our workshop in Coevorden, where we also carried out the FAT (Factory Acceptance Test) together with the installer. Our panel-building partner PS Nederland in Rijssen built the sub-distribution boards. Finally, we handled the entire delivery, from transport to the construction site through to hoisting and positioning the boards. Everything was delivered on schedule and to the agreed quality standards, in close collaboration with HOMIJ Technische Installaties.”

Boskalis Gebouw 6 under construction.
BIM implementation
“Unlike the main and sub-distribution boards, we had no previous experience with Hager’s busbar trunking systems,” says Mebius. “‘Gebouw 6’ is the first project on which we have used Hager busbar trunking, and it has been a success.” De Man adds: “Working closely with HOMIJ Technische Installaties, we established where the busbar trunking should run, taking into account factors such as the available installation space. We then developed the complete busbar trunking system in 3D/BIM and incorporated it into the building model, preventing clashes and rework on site. We selected 70 metres of 800-amp busbar trunking, installed in one continuous operation.”
Minimal space requirements
According to Mebius, choosing a busbar trunking system was a logical decision. “It significantly reduced the space required in the shaft. Instead of a ladder tray with cables and large feeder cables, a busbar trunking system measuring just 20 by 30 cm was sufficient. Installing an additional main distribution board in the plant room also meant that the cable runs could be made much shorter.” De Man adds: “Busbar trunking systems offer major advantages over cables in cable trays. They take up considerably less space, have greater short-circuit withstand capability and are less vulnerable to damage. Their low resistance and impedance also result in a low voltage drop. These advantages are clearly evident in this project too.”
A business enquiry for Hager? Get in touch
Who worked on it
Building 6 in Papendrecht
- designOPL architecten
- construction workVisser & Smit Bouw B.V.
- mechanical and electrical installationsHOMIJ Technische Installaties
- panel building partnerPS Nederland
Keep following this
Get an email when a new story is published. No account needed.
- ProjectBuilding 6
- SubjectBuilding services engineering
- CompanyOPL architecten
- CompanyVisser & Smit Bouw B.V.
- CompanyHOMIJ Technische Installaties
- CompanyPS Nederland
- CompanyHager