General

Finally, the ideal temperature and plenty of clean air

Text Lieke BousemaImage Diergaarde Blijdorp, Flow Care Installatietechniek, Plan2Be, Jabrulier en Western Airconditioning

Inmiddels is de nieuwe installatie enkele maanden in gebruik en Diergaarde Blijdorp merkt duidelijk verschil. “Het gaat heel goed met onze pinguïns.”
Inmiddels is de nieuwe installatie enkele maanden in gebruik en Diergaarde Blijdorp merkt duidelijk verschil. “Het gaat heel goed met onze pinguïns.”

New climate-control systems for the penguin enclosure at Diergaarde Blijdorp

Penguins are highly sensitive to temperature and humidity. If conditions remain outside their ideal range for a prolonged period, they can develop respiratory infections, often caused by fungal contamination. To prevent such infections and ensure a healthy, comfortable environment for the feathered residents, Diergaarde Blijdorp has replaced the climate-control system in its penguin enclosure. The Rotterdam zoo joined forces with specialist partners Flow Care Installatietechniek, Plan2Be, Jabrulier and Western Airconditioning. The aim? The ideal temperature and plenty of clean air.

Diergaarde Blijdorp is the only zoo in the Netherlands to house king penguins. The Oceanium is currently home to a colony of 25 adult king penguins and five chicks. The penguin enclosure also accommodates a large number of gentoo penguins. The maximum temperature for a penguin enclosure is 12°C, with relative humidity at around 40%. To achieve this, Diergaarde Blijdorp’s penguin enclosure has recently been fitted with a new air handling unit, chiller and control system. 

The air handling unit can move 10,500 m3/h of air, with a maximum outdoor air volume of 5,000 m3/h. This makes it possible to provide ‘free’ cooling for part of the year, when outdoor temperatures allow.

Restoring quality

Previously, the penguin enclosure had an air handling system with just a coarse air filter and two chillers. “The systems dated from 2000 and had reached the end of their technical service life,” says Randolph Streng, Technical Adviser and Oceanium Building Manager at Diergaarde Blijdorp. “The salty environment had corroded several system components, making the system unreliable. During the warm summer months, it could no longer maintain the required maximum temperature of 12°C. The air filtration was also inadequate. This not only affected the quality of the enclosure, but also the health and welfare of our penguins.” 

“Penguins have a body temperature of between 37 and 39°C,” says Streng. “Both king penguins and gentoo penguins are highly susceptible to fungi such as Aspergillus fumigatus, which are not found in their natural habitat in the Antarctic. The fungus thrives particularly at temperatures above 12°C. That is why it is important to keep the penguin enclosure below this temperature, and to filter the air properly so that the dust that attracts the fungi is effectively captured. We asked our regular installation partner Flow Care Installatietechniek to design a new system that meets the latest technical standards and achieves the temperatures our animal keepers require.” Another key requirement was to connect the new system to the Oceanium’s thermal energy storage system (WKO), installed in 2021, in line with Diergaarde Blijdorp’s sustainability ambitions. “This connection will not only improve the indoor climate for the penguins, but also make it possible to recreate the seasons.”

Supply air temperature: 4.0°C. The system can supply air at temperatures as low as -3.0°C.

Technical development team

Flow Care Installatietechniek has regularly carried out projects for Diergaarde Blijdorp for 20 years, delivering climate-control systems that have proven their performance and meet the Rotterdam zoo’s exotic specifications. “For climate control in the penguin enclosure, sufficient air movement, effective air purification and better temperature control were essential,” says Ewald Baars, managing director and owner of Flow Care Installatietechniek. “To meet these requirements and determine the right project specifications, I involved Richard Beeloo, director of consultancy Plan2Be. Together, we set up a technical development team with Melanie Bloem and Nedim Mehmedbegovic, both technical advisers to Diergaarde Blijdorp and highly familiar with the requirements for constructing and conditioning animal enclosures. Together with Melanie and Nedim, we translated the requirements of Diergaarde Blijdorp and its animal keepers into a technical design brief. We also carefully assessed the structural condition of the penguin enclosure. Where, for example, would be the best place to install the new air handling unit and chiller? And what would this mean for the system design? How could we connect to the WKO system? Richard then calculated the required air volumes and cooling capacities, and the technical design was developed and discussed over the course of just over a year.”  

From left: Ivo Hovius, François van Gorkom, Richard Beeloo, Ewald Baars and Randolph Streng.

Control and monitoring

The preparatory phase also involved identifying the required systems and suppliers, says Baars. “We regularly work with Jabrulier and Western Airconditioning, who shared their extensive knowledge and expertise and helped incorporate their products into the technical design. We also worked closely with B&S Meet- en regeltechniek to control the components. The new climate-control system in the penguin enclosure is connected via BACnet to the Oceanium’s SAUTER building management and automation system. This allows the new air handling unit and chiller, the opening of dampers and the operation of pumps to be controlled and monitored with great precision.”

Acoustic enclosure for the inverter compressor.

Corrosion-resistant air handling unit

“Following the cooling load and air volume calculations, we had to consider air circulation in the penguin enclosure at an early stage,” says Ivo Hovius, owner and sales manager at Jabrulier. “The enclosure has a salty environment, so at the very least the inside of the air handling unit needed to be corrosion-resistant. This would protect all the components exposed to recirculated air, for example. We have extensive experience building air handling units in 316 stainless steel, which are widely used in the offshore industry. Drawing on this experience, we recommended that not only the internal panels but as many components as possible should be made from 316 stainless steel.” Robust built-in components were also selected to ensure the reliability of the air handling unit. This included the cooling coil, which was given a seawater-resistant coating. “The cooling coil also has a wide fin spacing of 6 mm, because it provides deep cooling using ice water. Together with extensive detection measures, this keeps the risk of frost forming on the cooling coil to a minimum.”   

Control technology for operating the components.

Three-stage air filtration

An important requirement for Diergaarde Blijdorp and Flow Care Installatietechniek was to filter viruses and fungi efficiently in the penguin enclosure. “We looked at various filter combinations to supply the cleanest possible conditioned air,” says Hovius. “This led us to choose three-stage air filtration, which perfectly meets the penguins’ fresh air requirements. Both return air and fresh outdoor air first pass through an F7 air filter, which captures coarse dust and also protects against fine dust and pollen. The air then passes through an F9 air filter to remove fine and ultrafine particles, with low air resistance. Finally, before the cooling coil, an H14 HEPA filter provides extremely effective protection against pollen, viruses and fungi.”      

A chiller using R-32 refrigerant was selected specifically for the penguin enclosure, producing chilled water at -5°C.

Free cooling

The air handling unit can move 10,500 m3/h of air, with a maximum outdoor air volume of 5,000 m3/h, Hovius emphasises. “This makes it possible to provide ‘free’ cooling for part of the year, when outdoor temperatures allow.” The minimum setting is 2,500 m3/h. “The air handling unit is divided into return air, outdoor air and exhaust air sections, each using a fan of the same size and type. EC fans ensure energy-efficient operation.” Diergaarde Blijdorp has also stocked several spare fans, so components can be replaced quickly and easily in the event of a fault. 

The air handling unit is installed indoors, in a relatively warm room beneath a flat roof. Part of the façade had to be dismantled to install it. “Special transport was also needed to bring the three sections inside,” says Baars. “Because the room is warm, we paid extra attention to insulating the air handling unit.” Hovius adds: “Our WK-com THERMO offers the highest available thermal insulation class (T1) and cold bridge class (TB1). Extra insulation underneath and at the corners also prevents condensation at all times.”

New chiller

A sufficient supply of cold air is essential to keep the penguin enclosure at the right temperature 24/7. “That is why the air handling unit contains two cooling coils,” says Baars. “The first coil is connected to the WKO system, which provides base cooling. When more cooling is needed, the chiller supplied by Western Airconditioning kicks in. This chiller is connected to the second cooling coil and installed on the roof of the Oceanium.”

“Our chiller produces chilled water at -5°C,” says François van Gorkom, account manager at Western Airconditioning. “This can cool the air in the air handling unit from 12 to 4°C. At part load, we can cool it further, to a supply air temperature of -3°C.” The new chiller has a cooling capacity of 42 kW at this water temperature range.

The H14-class HEPA filters protect against viruses and fungi.

Low GWP, high seasonal efficiency

“A chiller using R-32 refrigerant (GWP = 675) was selected specifically for the penguin enclosure,” says Van Gorkom. “We fitted an inverter compressor to control the chiller precisely, modulating output from 100 to 10% in response to demand. This delivers a high seasonal efficiency of 4.7 and supports the project’s sustainability ambitions. Compared with a chiller using R-410A refrigerant, seasonal efficiency is more than >25% higher! The low-noise chiller is also fitted with additional internal acoustic insulation and operates almost silently.”

A seamless transition

The replacement of the climate control system was completed last summer. “We installed the new system first, then switched from the old setup to the new one in a single day last June,” says Baars. “The entire changeover went smoothly and quietly. The penguins didn’t notice a thing, other than that their habitat has become much more comfortable.” Streng adds: “The new system has now been in use for several months, and we can clearly see the difference. Our penguins are doing very well. We’ve even had 5 chicks hatch recently! The penguins can also enjoy the mountain of ice that is replenished in their habitat every day for much longer. It now remains visible and doesn’t melt within an hour. It’s also very welcome that the new setup saves us a lot of energy, and that our quarantine room can now be used effectively.”

Preventing infections

In addition to the main living area, with its pool and rock formations, the penguin habitat includes a nursery, a care kitchen and a quarantine room for new or sick penguins. “With the new air handling unit, we can now also operate the quarantine room,” says Streng. “A separate duct, separate controls and a separate extract fan ensure that air extracted from the quarantine room is not recirculated into the habitat, but is effectively discharged outside. This prevents contamination from the quarantine room.”

A successful partnership

A few months after the project was completed, Streng, Baars, Beeloo, Hovius and Van Gorkom reflect on a successful project marked by excellent collaboration and shared thinking. “Together, we delivered a fantastic project, with a system that is unique in its application,” concludes Streng. “Everyone’s input and advice were listened to carefully. That’s how we arrived together at the best solution for Diergaarde Blijdorp and its penguins.”    

Een zakelijke vraag aan Jabrulier? Get in touch

Companies in this story

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • SubjectGeneral
  • CompanyJabrulier
Share this article

Follow Installatie & Bouw Nederland

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.