Underfloor heating: comfort and efficiency depend on system control
Text Christobal van LeeuwenImage Pexels, Vecteezy, AI-assisted

Low temperatures, demanding design criteria
Underfloor heating is no longer an additional comfort feature. In new buildings, and increasingly in renovation projects, it is the primary heat emission system. This makes sense: low flow temperatures are an ideal match for heat pumps and provide even heat distribution. But low-temperature heating also sets high demands. Treating underfloor heating as a standard product will sooner or later lead to comfort complaints or reduced efficiency. The difference lies in the design, hydraulic balancing and control strategy.

Design starts with heat loss
A professional design starts with a heat loss calculation for each room. Only then should pipe spacing, circuit lengths and water temperatures be determined, not the other way round. The choice between primary heating, supplementary heating or combined heating and cooling determines the sizing. This should be based on a realistic, thermally unfavourable floor finish. Designing around the assumption that the floor will always be tiled is risky. If parquet or carpet is installed later, the required flow temperature will rise, directly affecting the efficiency of heat pumps and high-efficiency boilers. Efficiency is determined at the design stage.
Pipe spacing and floor build-up are key
Pipe spacing is not an installation detail but a comfort parameter. Excessive centre-to-centre spacing causes temperature striping and insufficient heat output. Spacing pipes too closely increases material use and pump power without delivering a proportionate comfort benefit. In living and office spaces, around thirty centimetres is considered the upper limit; pipes are laid closer together in bathrooms and comfort zones. The floor build-up also affects system performance:
• Wet systems provide thermal mass and stability, but respond slowly.
• Dry and renovation systems respond more quickly, but require precise coordination between heat distribution, floor finish and control.
• Milling grooves into the floor is a practical option, provided the existing screed is suitable and offers sufficient cover.
The lighter the floor build-up, the greater the influence of control and floor finish on the end result.
Comfort has its limits
Underfloor heating provides radiant comfort, but within physical limits. Under EN 1264, a maximum floor surface temperature of 29°C is generally applied in normally occupied rooms (at a room temperature of 20°C). Higher temperatures increase the risk of discomfort and damage to floor finishes. Designing for the maximum temperature treats the symptoms; designing within comfort limits means thinking in terms of the whole system.


The R-value determines efficiency
The thermal resistance of the floor finish directly affects the required water temperature. Dutch practical guidelines for homes often specify a maximum R-value of 0.15 m2K/W (ISSO). This is not an optional guideline. A higher R-value necessitates higher flow temperatures and reduces heat pump COP. In systems that combine underfloor heating and cooling, high resistance also limits cooling capacity. The choice of floor finish is therefore a system design parameter.
Where efficiency is lost
Comfort complaints are rarely caused by the pipe itself. They are almost always the result of system settings:
• incorrect flow rates for each circuit;
• on/off control in a slow-response system;
• an incorrectly set heating curve or mixing control;
• lack of hydraulic balancing.
Stable low-temperature operation is essential with heat pumps. Peak operation undermines efficiency. Zone control can improve comfort, but only if the hydraulic design and circuit layout are configured accordingly. Balancing is not a handover formality; it is part of the system design.
Cooling requires dew point control
Underfloor heating is increasingly used for both heating and cooling. The NEN-EN 1264 series of standards covers both applications. With cooling, the risk shifts from comfort to condensation. Without dew point monitoring, moisture can form on or within the floor structure. An adequate control and safety system is therefore essential.
Underfloor cooling provides comfort cooling; it is not a replacement for active air cooling. In many situations, additional ventilation or dehumidification is needed for safe cooling.
Compact plant rooms and Legionella
In renovation projects and new buildings, underfloor heating manifolds are often installed in compact plant rooms, sometimes alongside a heat pump and hot water cylinder. According to ISSO report 110973, this does not lead to an increased Legionella risk if certain conditions are met. The requirements are clear: flow temperatures below 35°C, sufficient separation between cold and hot water pipes in accordance with the Checklist Hotspots, and ventilation that keeps the room temperature below 25°C. Plant room layout is therefore an essential part of integrated design.
It is the system, not the pipe
Underfloor heating is not a standard component but an integrated system. Comfort and efficiency are determined not by the pipe in the floor, but by design choices, hydraulic balancing and control strategy. Anyone using low-temperature heating must control the system as a whole. Only then can comfort and efficiency truly be in balance.