Utrecht City Council opts for a fresh start with decentralised ventilation

Healthy air in the workplace

Fresh, healthy air is essential for maintaining staff concentration, productivity and wellbeing. Ventilation manufacturer Airmaster is pleased to contribute with decentralised ventilation units with heat recovery, combining healthy indoor air with heat retention. Without major building work. “The broad range of needs our Airmaster (AM) units can meet is demonstrated, for example, by our recent improvements to the air systems at three locations for Utrecht City Council,” says Jean-Paul Pil, Project Adviser at Airmaster. 

Indoor air quality at all three locations was suboptimal, says Pil. “CO2 meters showed that CO2 levels were rising too high. Utrecht City Council therefore asked Veolia Gebouwenbeheer to draw up a proposal for improvement. Veolia developed the plan in collaboration with consultancy De Vroome Advies. The companies opted for decentralised ventilation with our Airmaster units as the preferred solution.”

Under the Building Regulations, CO2 concentrations in office workspaces must always remain below 1,200 ppm. This limit is also applied in Utrecht City Council’s offices.

Flexible working environment

A particular feature of the office market is that spaces are often used for multiple purposes, says Pil. “What is a single large open-plan office today can be divided into separate office areas next week, and vice versa. The HVAC systems, including the ventilation system, need to be designed to accommodate this.” The decision was therefore made to use decentralised ventilation. “Several Airmaster units were fitted with demand-controlled systems and operate fully automatically and independently of one another. Aesthetics were also taken into account when choosing the ventilation system. The units have a sleek Scandinavian design and can be partially recessed into the suspended ceiling.” Outdoor air is supplied using the Coanda effect. The air is blown along the ceiling and then gradually falls downwards. “This ensures that fresh air is distributed optimally throughout the space and prevents draughts and complaints. In the summer months, Utrecht City Council also benefits from free night-time ventilation.”

Easy to fit

The first location to be upgraded was the Stadsbedrijven office on Tractieweg. “Three AM 300 units were installed in a large office almost thirty metres long,” says Pil. “Our ventilation units can be easily integrated into existing buildings. Connections can be made at the rear, side or top of the units, making them highly flexible. In this case, top connections were chosen, with fresh air supplied and stale air extracted through the roof.”

Several Airmaster units were fitted with demand-controlled systems and operate fully automatically and independently of one another.

Fully automatic control based on occupancy and CO2

Following the large office space, various meeting rooms were also fitted with AM 300 units. “We supplied a total of sixteen units for Tractieweg. All the units have a CO2 sensor and their own control panel, which allows staff to check the CO2 level in each room.” Under the Building Regulations, CO2 concentrations in office workspaces must always remain below 1,200 ppm. “This limit is also applied in Utrecht City Council’s offices. As occupancy in the offices and meeting rooms varies, and the rooms are not used at set times, control based on a CO2 sensor and motion detector was the best choice.” The ventilation unit starts running as soon as someone enters the room, says Pil. “The unit starts at a base ventilation capacity of 30%, and when more people enter and CO2 levels rise, the CO2 sensor automatically increases the ventilation capacity.”

Following the offices on Tractieweg, the city offices on Van Swindenstraat and Vaartscherijnstraat were also upgraded. Ventilation was installed not only in the offices but also in the canteen, where street-sweeper drivers, waste collectors, enforcement officers and other field staff take breaks and eat lunch. Given the high occupancy, an AM1000 unit was installed, says Pil. “We have developed a broad product range, with unit airflow rates ranging from 50 to 1,200 m3/h. This means we can offer a solution for any space. Until now, our ventilation solutions have been used mainly in schools, but this project shows that we are also a suitable partner for office refurbishments.”    

A business enquiry for Airmaster BV? Get in touch

Companies in this story

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ThemeHealthy indoor air
  • SubjectIndoor climate
  • CompanyAirmaster BV
Share this article

Follow Installatie & Bouw Nederland

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.