Decentralised ventilation units bring OBS Brinkschool up to Fresh Schools Class C

‘Achieving success with enjoyment’. OBS Brinkschool in Haren has recently expanded this ambition to include ‘Achieving success in a good and healthy indoor climate’. The state primary school in the centre of Haren has been fitted with 10 Airmaster AM 800 ventilation units, which maintain a good indoor climate in every season, with fully demand-controlled operation.

Danish ventilation manufacturer Airmaster has been providing healthy indoor air and optimum thermal comfort in offices, nurseries and schools, among other settings, for more than 30 years. “Opening the windows is of course the easiest way to ventilate,” says project adviser Jean-Paul Pil. “But to get ventilation properly under control in every season, structural measures are needed. OBS Brinkschool in Haren was aware of this too.” The primary school is currently housed in an older building, but will eventually move to a new building, IKC Rummerinkhof, around 500 metres away. However, the school board did not want to wait for the new building. “To ensure a healthy indoor climate for all pupils and teaching staff right now, they decided to tackle the indoor climate.”
Inspection and advice at the project site
During the mini-tender that followed, several contractors contacted Airmaster. The project was ultimately awarded to IBV Venema. Before submitting a final quotation, Pil insisted on arranging a site inspection and consultation with the contractor. He explains: “Renovation projects almost always uncover problems that call for creative solutions. For example, there may be structural beams or light fittings in the way that could adversely affect the units’ air throw. To ensure the ventilation system works optimally, it is also important to install the units in the right place in the room. We also advised the contractor on the most suitable way to suspend the ventilation units.”
Demand-controlled operation prevents ‘over-ventilation’
To meet the Fresh Schools Class C requirement, ventilation capacity must be at least 21.6 m3/h per person. “Based on an occupancy of 30 pupils plus 1 teacher, each classroom therefore needed a minimum airflow of 670 m3/h,” says Pil. “Our AM800 units, with a maximum airflow of 725 m3/h, comfortably meet this standard. To avoid ‘over-ventilation’, all the units are equipped with demand-controlled operation. Each unit has a CO2 sensor that automatically adjusts the airflow to the number of pupils in the classroom.” The decentralised units are easy to monitor and control room by room, thanks to a wall-mounted control panel with clear traffic-light indicators (colour codes) and a ppm readout. “As the school did not yet have a building management system, we also offered our internet-enabled Airlinq® Online control system. This web platform allows the 10 units to be managed and operated remotely. To ensure the system was installed and used perfectly, we met with IBV Venema again.”
Optimum thermal comfort in winter and summer
The Airmaster units deliver high heat recovery efficiency, of more than 85 per cent. “On cold winter days, fresh outdoor air is preheated before being supplied to the classroom,” says Pil. “This prevents draughts and reduces heating costs. When it gets warmer outside, a bypass opens automatically, allowing outdoor air to be supplied directly to the room. The control system for each unit also includes night cooling as standard. This function supplies fresh air at night on hot days, so pupils arrive in a cool classroom in the morning.”
First reactions are positive
The Airmaster ventilation units for OBS Brinkschool were delivered to Haren just in time and ready to plug and play. Airmaster monitored the installation throughout and was also responsible for checking and commissioning the system. “The units were put into use after the 2021/2022 Christmas holidays,” says Pil. “The first reactions have been very positive. Some teachers still need to get used to the fact that the windows no longer need to be opened. They really appreciate being able to check the CO2 level in their classroom easily on the control panel. It gives them peace of mind without compromising thermal comfort.”
Project details
Client
OBS Brinkschool
Contractor
IBV Venema
Ventilation units
Airmaster
A business enquiry for Airmaster BV? Get in touch
Who worked on it
OBS Brinkschool in Oss
- ventilation units
Airmaster - InstallerIBV Venema
Keep following this
Get an email when a new story is published. No account needed.
- ProjectOBS Brinkschool
- ThemeHealthy indoor air
- SubjectBuilding services engineering
- CompanyAirmaster BV
- CompanyIBV Venema